OM-10 Series

Watt Transducers | OM-10 Series

Watt Transducers

imagem meramente ilustrativa

1 ano de garantia
  • 0.2% Accuracy
  • Isolated
  • Models Available with 4-20 mA or 0-1 mA Outputs

Descrição

The OM10 Series has been discontinued. Please see the DRA-WVT-3 Series as a possible alternative or contact our Data Acquisition Engineering Department.

OMEGA’s OM10 Series watt transducers accept ac voltages and currents to produce a conditioned dc process signal output representing wattage. Single, dual, and three element models are available to accommodate a variety of wiring configurations. For larger input voltages and currents, the OM10 may also be used with OMEGA’s voltage and current transformers.

SPECIFICATIONS
Accuracy: 0.2% of reading
Sustained Input Overrange: Voltage, 120% continuous, 150% for 5 seconds; current, 200% continuous, 1000% for 5 seconds
Outputs: 0 to 1 mA DC: into 10 kΩ 10 Vdc compliance; 4 to 20 mA into 750 Ω max 15 Vdc compliance
Output Calibration: 120 Vac/5 A = 0 to 500 W/element; 240 Vac/5 A = 0 to 1000 W/element
Zero Adjust: ±5% min
Span Adjust: ±10% min
Response Time: <400 msec 0 to 99% of full scale
Power Consumption: 5 VA max
Isolation: Input to output: 2500 Vac, 60 Hz, 1min; input to power: 2500 Vac, 60 Hz, 1 min; input to case: 2500 Vac, 60 Hz, 1 min; power to output: 2000 Vac, 60 Hz, 1 min; power to case: 2000 Vac, 60 Hz, 1 min; output to case: 500 Vac, 60 Hz, 1 min
Dimensions: 119.8 H x 133 W x 95.7 mm D (4.717 x 5.236 x 3.769")