Isolated DIN Rail Signal Conditioner

DRSL-DC3

Isolated DIN Rail Signal Conditioner | DRSL-DC3

Isolated DIN Rail Signal Conditioner

imagem meramente ilustrativa

1 ano de garantia CE RoHS
  • Isolation and Conversion of Process Voltage or Current Signals
  • Slimline Housing—Only 6 mm (0.24") Wide
  • Multiple Signal Ranges (DIP-Switch Selectable)
  • High Accuracy, <0.2% of Span
  • Fast Response Time <7 ms
Intrumentos para Medição e Controle de Processos - Ver Produtos Relacionados

Descrição

The DRSL-DC3 isolated DIN rail signal conditioner provides a competitive choice in terms of both price and technology for galvanic isolation of process voltage or current signals to SCADA systems or PLC equipment. The DRSL-DC3 can be used for signal conversion of standard process voltage or current signals. The unit offers isolation between input, output and supply, provides surge suppression and protects control systems from transients and noise.

The DRSL-DC3 also eliminates ground loops and can be used for measuring floating signals. Low power consumption facilitates DIN rail mounting without the need for any air gap. Factory calibrated measurement ranges are easily configured via DIP switches. The unit operates over a wide temperature range from -25 to 70°C (-13 to 158°F).

SPECIFICATIONS
INPUT
Current Input
    Measurement Range: 0 to 20.5 mA
    Functional Range: 0 to 23 mA
    Programmable Measurement Ranges: 0 to 20 mA and 4 to 20 mA
    Input Voltage Drop: < 1.5V
Voltage Input
    Measurement Range: 0 to 10.25V
    Functional Range: 0 to 11.5V/ 0 to 5.75V
    Programmable Measurement Ranges: 0 to 5V, 1 to 5V, 0 to 10V, 2 to 10V
    Input Resistance: ≥500 kΩ

OUTPUT
Current Output
    Signal Range: 0 to 20.5 mA (span)
    Programmable Signal Ranges: 0 to 20 mA and 4 to 20 mA
    Load: 23 mA/600 Ω max
    Load Stability: ≤0.01% of span/ 100 Ω
    Current Limit: ≤28 mA
Voltage Output
    Signal Range: 0 to 10V
    Programmable Signal Ranges: 0 to 10, 2 to 10, 0 to 5 and 1 to 5V
    Load: >10 kΩ min

GENERAL
Supply Voltage (via Power Rail or Connectors): 16.8 to 31.2 Vdc
Power Consumption: 0.8 W max
Internal Consumption: 0.4 W typical/ 0.65 W max
Isolation: Input/Output/Supply
Isolation Voltage (Test): 2.5 kVac
Isolation Voltage (Working): 300 Vac
MTBF: >249 years, according to IEC 61709 (SN29500)
Signal/Noise Ratio: >60 dB
Response Time (0 to 90%, 100 to 10%): <7 ms
Span: Corresponds to the presently selected DIP switch output range
Accuracy: <±0.2% of span
Temperature Coefficient: <±0.015% of span/°C
EMC Immunity Influence: <±0.5% of span
Extended EMC Immunity
    NAMUR NE 21, A Criterion, Burst: <±1% of span

ENVIRONMENTAL
Operating Temperature: -25 to 70°C (-13 to 158°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Calibration Temperature: 20 to 28°C (68 to 82°F)
Relative Humidity: 0 to 95% RH non-condensing
Protection Degree: IP20
Installation Area: Pollution degree 2 and measurement/overvoltage category II

MECHANICAL
Dimensions: 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5”)
Weight: 70 g (0.15 lb) approx
DIN Rail Type: DIN EN 60715 - 35 mm
Wire Size: 0.13 x 2.5 mm2/AWG 26 to 12 stranded wire
Screw Terminal Torque: 0.5 Nm

Manuais:

Baixar Installation Guide for Signal Conditioners
Baixar DIN Rail Isolators and Signal Conditioners
We noticed you are from the US. Visit your local site for regional offers and live support.