Carrinho  |  Contato  |  Suporte  | 
Atendimento e Vendas 0800-773-2874
e-mail:vendas@br.omega.com

DIN Rail Input Loop-Powered Isolators

DRSL-LPI_Series

Loop-Powered Isolators - DIN Rail Input for galvanic isolation | DRSL-LPI_Series
Novo

imagem meramente ilustrativa

Veja lista de preços e produtos abaixo

1 ano de garantia CE RoHS
  • 1 Channel (DRSL-LPI-1) or 2 Channel (DRSL-LPI-2) Input Loop Powered Isolators
  • Powered by the Analog Input Current Signal Loop
  • 1:1 Signal Ratio
  • Low Input Voltage Drop
  • Fast Response Time <5 ms
  • High Conversion Accuracy, <0.1% of Span (0 to 20.5 mA)
  • Slimline 6 mm (0.24") Housing
Intrumentos para Medição e Controle de Processos - Ver Produtos Relacionados

Descrição

The DRSL-LPI Series DIN rail input loop powered isolators provide a competitive choice in terms of both price and technology for galvanic isolation of current signals to SCADA systems or PLC equipment. These units provide isolation and 1:1 conversion of standard current signals and are powered by the analog input current signal loop.

The DRSL-LPI series offers isolation between input and output, provides surge suppression and protects control systems from transients and noise. These units also eliminate ground loops and can be used for measuring floating signals. Low power consumption facilitates DIN rail mounting without the need for any air gap. Measurement ranges are factory calibrated. These isolators operates over a wide temperature range from -25 to 70°C (-13 to 158°F).

SPECIFICATIONS
NUMBER OF CHANNELS
    DRSL-LPI-1: 1
    DRSL-LPI-2: 2
CURRENT INPUT
Signal Range (Input to Output): 0 to 20.5 mA
Signal Conversion: 1 to 1
Functional Range: 0 to 23 mA (NAMUR NE43 compliant)
Start up Current: 10 µA typical
Input Overload: 50 mA max
Input to Output Voltage Drop: 1.25V + (0.015 x Vout) where Vout = Iout x Routput, typical
Input Voltage Drop: (Unit voltage drop) + Vout
CURRENT OUTPUT
    Output Load: 600Ω max
    Output Load Stability: <0.01% of span/100 Ω (span = 0 to 20 mA)
    Voltage Limit: 17.5V

GENERAL
Internal Consumption: 30 mW per channel
Isolation Voltage (Test): 2.5 kVac
Isolation Voltage (Working): 300 Vac
Signal/Noise Ratio: >60 dB
Cut-Off Frequency (3 dB): 100 Hz
Response Time (0 to 90%, 100 to 10%): <5 ms
Absolute Accuracy (at 25°C): ≤±10 µA + 0.05% of max value of selected span
Temperature Coefficient: ≤±2 µA/°C
EMC Immunity Influence: <±0.5% of span
Extended EMC Immunity NAMUR NE 21, A Criterion, Burst: <±1% of span

ENVIRONMENTAL
Operating Temperature: -25 to 70°C (-13 to 158°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Calibration Temperature: 20 to 28°C (68 to 82°F)
Relative Humidity: 0 to 95% RH non-condensing
Protection Degree: IP20
Installation Area: Pollution degree 2 and measurement/overvoltage category II

MECHANICAL
Dimensions: 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5")
Weight: 70 g (0.15 lb) approx
DIN Rail Type: DIN EN 60715 - 35 mm
Wire Size: 0.13 x 2.5 mm²/AWG 26 to 12 stranded wire
Screw Terminal Torque: 0.5 Nm
Ver Modelos e Preços(Especifique o número do modelo)

O que outras pessoas compraram: Quando você vir este ícone, clique nele para expandir a lista de produtos que outras pessoas tenham comprado quando compraram este modelo.

Código de Produto/Desc.
Qtd
RoHS
Descrição
Quick Ship
  
DRSL-LPI-1
R$910,00
Disponível em: 1 semana
conformidade RoHS
DIN rail input loop-powered isolator, 1 channel
Quick Ship
  
DRSL-LPI-2
R$1.265,00
Disponível em: Em estoque
conformidade RoHS
DIN rail input loop-powered isolator, 2 channel
Accessories
Quick Ship
Clique para expandir / minimizar uma lista do que os outros compraram comRAIL-35-1
RAIL-35-1
R$84,00
Disponível em: Em estoque
conformidade RoHS indeterminada
35 mm (1.4") DIN rail, 1 m (3.3') length
Quick Ship
  
DRSL-MOD-STOP
R$43,50
Disponível em: Em estoque
conformidade RoHS
Module stop (screwed onto DIN rail to support and hold mounted devices)
Preços indicados em Reais e já incluem todos os impostos e taxas de acordo com a legislação vigente. Exemplo de Pedido: (1) DRSL-LPI-1 DIN rail input loop-powered isolator, 1 channel, R$910,00  plus (1) DRSL-MOD-STOP Module stop (screwed onto DIN rail to support and hold mounted devices), R$43,50  plus (1) RAIL-35-1 35 mm (1.4, R$84,00, R$910,00 + 43,50 + 84,00 = R$1.037,50

Manuais:

Baixar Installation Guide for Signal Conditioners
Baixar DIN Rail Loop Powered Isolators